STS 16A

The STS-16 provides redundant power and ensure high availability for entry-level networking equipment, high-density server and blade environments.


Best Suited for: Banking, financial and insurance, data center, education, healthcare, government.


DOCUMENTS & DOWNLOADS

DOCUMENTS & DOWNLOADS

DOCUMENTS & DOWNLOADS

Description
  • Horizontal and vertical Rack-Mounting capability
  • Break before make transfer mode
  • Seamless power transfer
  • Redundant power supply (from input Source 1 & Source 2)
  • Wide range of input and output connections
  • Different setting to adjust the voltage failure sensing level (+/- 12% ~ +/-20%)
  • Ability to be supplied by N/Ph1 and N/Ph2 from a three phase supply
  • Multiple outlets eliminating the need for a secondary rack
  • PDU Effective solution for maintenance bypass needs
  • Robust out-of-phase switching
  • Back feed protection (according EN62310-1)
  • Complete protection for overload and short-circuit
  • LED indicators
  • Visual and audible alarm
  • Continuous source and output current detection
  • RPO contact
  • Smart RS-232, dry contact and SNMP communication port

DOCUMENTS & DOWNLOADS

SPECIFICATION

odelSTS - 16
 
Input 
Voltage
ATS Working Range
Input Voltage acceptable window
Nominal Current
Frequency
Inlet
220/230/240V Selectable
160~290V
+/-12%~+/-20% adjustable (default:+/-12%)
16 Amp
50 or 60Hz +/- 15%
IEC 320-C20x2
 
Ouput 
Voltage
Frequency (Back up Mode)
Output Current
Transfer Time
Outlet
220/230/240V Selectable
50 or 60Hz
16 Amp
1 ms typical
IEC 320-C19x1/IEC320-C13-3x2
 
Protection 
Overload Capability
Output Short Circuit
101~125% for 12 sec, 126~150% for 8 sec, 151~210% for 4 sec, 211~300% for 2 sec
Complete protection by input fuse (with fuse holder accessible)
 
System

Display/Warning
 
LED Indicators
Fault (F1 Indicator)
Preferred source (S1/S2), Line status (S1/S2), Output power state (supply load from S1/S2), fault conditions
Overload fault, Output short circuit, Input source relay fault, EPO active
 
Communication 
RS-232, Dry contact
SNMP Card (Optional)
Monitoring of system information
Remote Monitoring capabilities in SNMP based networks
 
Physical 
Net Weight kg (lbs)
Dimensions (WxDxH) mm (inch)
Color
Structure
8(17.6)
430 x 315 x 44 (16.9" x 12.3" x 1.73")
Silver RAL 9006
Rack Mount Unit (1 U)
 
Environment 
Operating Temperature
Storage Temperature
Operating Humidity
Altitude
Audible Noise
Cooling
IP Protection
0°C to 40°C
-25°C to 70°C
20-85% humidity non-condensing
≤1000m
25dBA (max.)
Natural cooling
IP30
 
Standards & Certifications 
Safety
EMC (EMS/EMI)
Marking & Certifications
EN 62310-1
IEC 62310-2,C1;IEC61000-4-2 level 3;IEC61000-4-3 level 2 (Lab.); IEC61000-4-4 level 2; IEC61000-4-5 level 3; IEC61000-2-2 LF Immunity; IEC61000-4-6 level 2(Lab.); IEC61000-3-2 harmonic (Lab.); IEC61000-3-3 Flicks
CE