VX 1~10K

The VX UPS is an online double conversion UPS available from 1kVA to 10kVA with an output power factor 0.9. It is equipped with DSP technology for increased power efficiency and power density. The VX series has USB and RS-232 communication ports as standard, with a built-in intelligent slot for optional protocol converters (e.g. SNMP…). The VX Series is the best solution for different applications: servers and networking devices, control systems, video surveillance systems…


Best Suited for: Banking, financial and insurance, data center, education, healthcare, government.


DOCUMENTS & DOWNLOADS

DOCUMENTS & DOWNLOADS

DOCUMENTS & DOWNLOADS

Description
  • True Online Double Conversion Design
  • Pure Sine Wave Output
  • Fully Digitized Microprocessor Control
  • DSP Technology (for 6K and 10K models)
  • Output Power Factor 0.9
  • Active Input Power Factor Correction (PFC 0.99)
  • 50/60 Hz Frequency Converter
  • Wide Input Voltage Range
  • Built-in Automatic Bypass
  • Generator Compatible
  • Emergency Power Off Function (EPO)
  • Cold Start Function (DC Power On)
  • Advanced Battery Management (ABM Technology)
  • Eco Mode For Energy Saving
  • Programmable Power Management Outlets
  • Multi-Function LCD Display
  • Software Monitoring & Control
  • Smart SNMP/USB/RS-232/AS-400 Communication Slots*

 * Optional Features

DOCUMENTS & DOWNLOADS

ModelVX 1K
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
1000VA
220V, 230V, 240V, 1Ø 2Wires
40~70Hz
176-300 VAC at 100% load, 110-300 VAC at 50% load
>99%
<5%
 
Ouput 
Active Power @ PF=0.9
Voltage (on battery)
Frequency (on battery)
Transfer Time
Efficiency
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
900W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.2%
0 ms
93%
Online double conversion design
Pure Sinewave
≤3% (linear load), ≤5% (non linear load)
3:1
 
Protection 
Overload Protection
Short Circuit Protection
110% for 10min, 130% for 1min, >130% for 3sec
UPS output cuts off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
 
Alarm 
Battery mode
Low battery
Overload
Fault
Sounding every 4 second
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
DC Voltage
Charging Current
Back up time(1/2 Load)
12V 9Ah
4 hours to 90% Full capacity
24VDC
1A
10~15 min depending on load
 
Communication 
USB or RS-232
SNMP*
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
145x282x220mm
9.8Kg(21.6lb)
 
Environment 
Operating Temperature
Storage Temperature
Altitude
Audible noise
Relative Humidity
0 - 40 °C / 32 ~ 104°F
-20 ~ 50°C / -4 ~ 122°F
1,500 meters max
<50dBA at 1 Meter
20 to 90% humidity (non-condensing)
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, & services
Environment
Marking & Certifications
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950
IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22, EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 - Subpart B -
ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
 
* For optional features
***Product specifications are subject to change without further notice
ModelVX 2K
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
2000VA
220V, 230V, 240V, 1Ø 2Wires
40~70Hz
176-300 VAC at 100% load, 110-300 VAC at 50% load
>99%
<5%
 
Ouput 
Active Power @ PF=0.9
Voltage (on battery)
Frequency (on battery)
Transfer Time
Efficiency
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
1800W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.2%
0 ms
93%
Online double conversion design
Pure Sinewave
≤3% (linear load), ≤5% (non linear load)
3:1
 
Protection 
Overload Protection
Short Circuit Protection
110% for 10min, 130% for 1min, >130% for 3sec
UPS output cut off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
 
Alarm 
Battery mode
Low battery
Overload
Fault
Sounding every 4 second
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
DC Voltage
Charging Current
Back up time(1/2 Load)
12V 9Ah
4 hours to 90% Full capacity
48VDC
1A
10~15 min depending on load
 
Communication 
USB or RS-232
SNMP*
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
145x397x220mm
17Kg(37.4lbs)
 
Environment 
Operating Temperature
Storage Temperature
Altitude
Audible noise
Relative Humidity
0 - 40 °C / 32 ~ 104°F
-20 ~ 50°C / -4 ~ 122°F
1,500 meters max
<50dBA at 1 Meter
20 to 90% humidity (non-condensing)
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, & services
Environment
Marking & Certifications
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950
IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22, EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 - Subpart B -
ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
 
* For optional features
***Product specifications are subject to change without further notice
 
 
ModelVX 3K
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
3000VA
220V, 230V, 240V, 1Ø 2Wires
40~70Hz
176-300 VAC at 100% load, 110-300 VAC at 50% load
>99%
<5%
 
Ouput 
Active Power @ PF=0.9
Voltage (on battery)
Frequency (on battery)
Transfer Time
Efficiency
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
2700W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.2%
0 ms
94%
Online double conversion design
Pure Sinewave
≤3% (linear load), ≤5% (non linear load)
3:1
 
Protection 
Overload Protection
Short Circuit Protection
110% for 10min, 130% for 1min, >130% for 3sec
UPS output cut off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
 
Alarm 
Battery mode
Low battery
Overload
Fault
Sounding every 4 second
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
DC Voltage
Charging Current
Back up time(1/2 Load)
12V 9Ah
4 hours to 90% Full capacity
72VDC
1A
10~15 min depending on load
 
Communication 
USB or RS-232
SNMP*
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
190x421x318mm
27.6Kg(60.7lbs)
 
Environment 
Operating Temperature
Storage Temperature
Altitude
Audible noise
Relative Humidity
0 - 40 °C / 32 ~ 104°F
-20 ~ 50°C / -4 ~ 122°F
1,500 meters max
<50dBA at 1 Meter
20 to 90% humidity (non-condensing)
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, & services
Environment
Marking & Certifications
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950
IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22, EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 - Subpart B -
ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
 
* For optional features

***Product specifications are subject to change without further notice
ModelVX 6K
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
6000VA
220V, 230V, 240V, 1Ø 2Wires
40~70Hz
176-300 VAC at 100% load, 110-300 VAC at 50% load
>99%
<5%
 
Ouput 
Active Power @ PF=0.9
Voltage (on battery)
Frequency (on battery)
Transfer Time
Efficiency
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
5400W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.2%
0 ms
>94%
Online double conversion design
Pure Sinewave
≤3% (linear load), ≤5% (non linear load)
3:1
 
Protection 
Overload Protection
Short Circuit Protection
110% for 30min, 130% for 5min, >130% for 10sec
UPS output cut off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
 
Alarm 
Battery mode
Low battery
Overload
Fault
Sounding every 4 second
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
DC Voltage
Charging Current
Back up time(1/2 Load)
12V 9Ah
5 hours to 90% capacity
192VDC
1-2A (adjustable)
10~15 min depending on load
 
Communication 
USB or RS-232
SNMP*
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
190x369x688mm
61kg(134lbs)
 
Environment 
Operating Temperature
Storage Temperature
Altitude
Audible noise
Relative Humidity
0 - 40 °C / 32 ~ 104°F
-20 ~ 50°C / -4 ~ 122°F
1,500 meters max
<55dBA at 1 Meter
0 ~ 95% humidity, non-condensing
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, & services
Environment
Marking & Certifications
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950
IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22, EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 - Subpart B -
ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
 
* For optional features
***Product specifications are subject to change without further notice
 
 
ModelVX 10K
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
10000VA
220V, 230V, 240V, 1Ø 2Wires
40~70Hz
176-300 VAC at 100% load, 110-300 VAC at 50% load
>99%
<5%
 
Ouput 
Active Power @ PF=0.9
Voltage (on battery)
Frequency (on battery)
Transfer Time
Efficiency
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
9000W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.2%
0 ms
>95%
Online double conversion design
Pure Sinewave
≤3% (linear load), ≤5% (non linear load)
3:1
 
Protection 
Overload Protection
Short Circuit Protection
110% for 30min, 130% for 5min, >130% for 10sec
UPS output cut off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
 
Alarm 
Battery mode
Low battery
Overload
Fault
Sounding every 4 second
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
DC Voltage
Charging Current
Back up time(1/2 Load)
12V 9Ah
5 hours to 90% capacity
192VDC
1-2A (adjustable)
10~15 min depending on load
 
Communication 
USB or RS-232
SNMP*
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
190x442x688mm
66kg(145lbs)
 
Environment 
Operating Temperature
Storage Temperature
Altitude
Audible noise
Relative Humidity
0 - 40 °C / 32 ~ 104°F
-20 ~ 50°C / -4 ~ 122°F
1,500 meters max
<58dBA at 1 Meter
0 ~ 95% humidity, non-condensing
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, & services
Environment
Marking & Certifications
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950
IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22, EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 - Subpart B -
ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
 
* For optional features
***Product specifications are subject to change without further notice