| Input | | | Rating | | Voltage | | Frequency | | Voltage range | | Power Factor | | THDi |
| | 3000 VA | | 220V, 230V, 240V, 1Ø 2Wires | | 40 to 70 Hz | | 176-300 VAC at 100% load, 110-300 VAC at 50% load | | >99% | | ≤3% |
|
|
| |
| Output | | | Active Power with cosφ=1 | | Voltage (on battery) | | Frequency (on battery) | | Transfer Time | | UPS Design Technology | | Output Wave Form | | Total Harmonic distortion (THD) | | Crest Factor |
| | 3000W | | 220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires | | 50/60 Hz +/-0.1% | | 0 ms | | Online double conversion design | | Pure Sinewave | | ≤2% (linear load), ≤4% (non linear load) | | 3:1 |
|
|
| |
|
| |
| Protection | | | Overload Protection | | Short Circuit Protection |
| | 110% for 10min, 130% for 1min, >130% for 3sec | | UPS output cut off immediately using input fuse/circuit breaker protection |
|
|
| |
| System Display | | | | UPS Status, Load level, Battery level, Input/Output voltage, Discharge time,and Fault indicators |
|
|
| |
| Alarm | | | Battery mode | | Low battery | | Overload | | Fault |
| | Sounding every 4 second | | Sounding every second | | Sounding twice every second | | Continuously sounding |
|
|
| |
| Battery | | | Battery Type | | Typical Recharge Time | | Charging Current | | DC Voltage | | Extended Back up time |
| | 12V 9Ah | | 4 hours to 90% capacity | | 1.5A | | 72VDC | | 10~15 min depending on load |
|
|
| |
| Communication | | | USB, RS-232, AS-400¹ | | SNMP¹ | | Compatibility |
| | Interface with power management software | | Power Management from SNMP manager and web browser | | Supports Windows family, Linux, Unix and Mac |
|
|
| |
| Physical | | | W x D x H mm | | Net Weight Kgs |
| |
|
| |
| Environment | | | Ambient operation | | Audible noise |
| | Maximum elevation at 1000m, 0 to 40°C, 20 to 95% humidity (non-condensing) | | <50dBA at 1 Meter |
|
|
| |
| Standards & Certifications | | | Performance | | Safety | | EMC (EMS / EMI) | | Design, production, & services | | Environment | | Marking & Certifications |
| | EN50091-3/IEC 62040-3 | | UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950 | IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22, EN 50091-2/IEC62040-2 Class A, EN 55022/B,FCC 47 part 15 - Subpart B - | | ISO 9001 | | ISO 14001 certified company | | CE, TUV/GS, UL, cUL, c-Tick |
|
|
*In LV system, only 12V/7Ah x 3 for 1K model and 12V/7Ah x 6 for 3K model are available. NOTE 1: Derate to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC. NOTE 2: If the UPS is installed or used in a place where the altitude is above than the rated altitude, the output power must be derated one percent per 100m. NOTE 3: For Long run models (6kVA~10kVA), When using internal batteries from 18-19, the unit will de-rate according to below formula: P=Prating x N/20 ** For optional features ***Product specifications are subject to change without further notice |