MXRM31 10~20K

The MXRM31 UPS is a 3-phase In/1-phase Out online double conversion UPS available from 10kVA to 20kVA with an output power factor 1. It is designed for use within rack-based enclosures. It provides ultimate performance in power protection and redundancy for critical systems requiring high power availability. The MXRM31 series has USB and RS-232 communication ports as standard, with a built-in intelligent slot for optional protocol converters (e.g. SNMP…)


Best Suited for: Banking, financial and insurance, server rooms, data centers, education, healthcare, government.


DOCUMENTS & DOWNLOADS

DOCUMENTS & DOWNLOADS

DOCUMENTS & DOWNLOADS

Description
  • 3-phase In/1-phase Out
  • True Online Double Conversion Design
  • Pure Sine Wave Output
  • Fully Digitized Microprocessor Control
  • DSP Technology Output Power Factor 1
  • Active Input Power Factor Correction (PFC 0.99)
  • 50/60 Hz Frequency Converter
  • Wide Input Voltage Range
  • Emergency Power Off Function (EPO)
  • Cold Start Function (DC Power On)
  • Advanced Battery Management (ABM Technology)
  • Automatic Diagnostics & Battery Check
  • High Overload Capability and Enhanced Short Circuit Protection
  • Eco Mode For Energy Saving
  • Isolation Transformer*
  • Programmable Power Management Outlets
  • Multi-Function LCD Display

 * Optional Features

DOCUMENTS & DOWNLOADS

ModelMXRM 10K 31
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
10000VA
380V, 400V, 415V (selectable) , 3Φ4wires
40 to 70 Hz
305-478 VAC at 100% load, 190-520 VAC at 50% load
>99%
<3%
 
Output 
Active Power @ PF=1
Voltage (on battery)
Frequency (on battery)
Transfer Time
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
10000W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.1%
0 ms
Online double conversion design
Pure Sinewave
≤2% (linear load), ≤5% (non linear load)
3:1
 
Efficiency 
AC Mode
Battery Mode
95%
94%
 
Protection 
Overload Protection
Short Circuit Protection
110% for 10min, 130% for 1min, >130% for 3sec
UPS output cut off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
UPS status, load level, battery level, input/output voltage, discharge time and fault indicators
 
Alarm 
Battery Mode
Low Battery
Overload
Fault
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
Charging Current
Battery number
Back up time(1/2 Load)
12V 9Ah
9 hours to 90% capacity
1A
20
10~15 min depending on load
 
Communication 
USB, RS-232, AS-400**
SNMP**
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
UPS: 438 X 668 x 133[3U] Battery Pack:438 x 580 x 133[3U]
UPS: 22(48.4lbs) Battery: 63(138.6lbs)
 
Environment 
Ambient operation
Audible noise
Maximum elevation at 1000m, 0 to 40°C, 0 to 95% humidity (non-condensing)
<60dBA at 1 Meter
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, and services
Environment
Marking & Certifications
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950

IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22,
EN 50091-2/IEC62040-2 Class A EN 55022/B,FCC 47 part 15 - Subpart B -

ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P=Prating x N/20
NOTE 1: Derate to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
NOTE 2: If the UPS is installed or used in a place where the altitude is above than the rated altitude, the output power must be derated one percent per 100m.
** For optional features
***Product specifications are subject to change without further notice
 
 
ModelMXRM 15K 31
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
15000VA
380V, 400V, 415V (selectable) , 3Φ4wires
40 to 70 Hz
305-478 VAC at 100% load, 190-520 VAC at 50% load
>99%
<3%
 
Output 
Active Power @ PF=1
Voltage (on battery)
Frequency (on battery)
Transfer Time
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
15000W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.1%
0 ms
Online double conversion design
Pure Sinewave
≤2% (linear load), ≤5% (non linear load)
3:1
 
Efficiency 
AC Mode
Battery Mode
96%
95%
 
Protection 
Overload Protection
Short Circuit Protection
110% for 10min, 130% for 1min, >130% for 3sec
UPS output cut off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
UPS status, load level, battery level, input/output voltage, discharge time and fault indicators
 
Alarm 
Battery Mode
Low Battery
Overload
Fault
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
Charging Current
Battery number
Back up time(1/2 Load)
12V 9Ah
9 hours to 90% capacity
2A
20 x2 strings
10~15 min depending on load
 
Communication 
USB, RS-232, AS-400**
SNMP**
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
UPS: 438 X 668 x 266[6U] Battery Pack:438 x 580 x 133[3U] x 2 pcs
UPS: 45 (99lbs) Battery: 63 (138.6lbs)x2pcs
 
Environment 
Ambient operation
Audible noise
Maximum elevation at 1000m, 0 to 40°C, 0 to 95% humidity (non-condensing)
<65dBA at 1 Meter
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, and services
Environment
Marking & Certifications
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950

IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22,
EN 50091-2/IEC62040-2 Class A EN 55022/B,FCC 47 part 15 - Subpart B -

ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P=Prating x N/20
NOTE 1: Derate to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
NOTE 2: If the UPS is installed or used in a place where the altitude is above than the rated altitude, the output power must be derated one percent per 100m.
** For optional features
***Product specifications are subject to change without further notice
 
 
 
 
ModelMXRM 20K 31
 
Input 
Rating
Voltage
Frequency
Voltage range
Power Factor
THDi
20000VA
380V, 400V, 415V (selectable) , 3Φ4wires
40 to 70 Hz
305-478 VAC at 100% load, 190-520 VAC at 50% load
>99%
<3%
 
Output 
Active Power @ PF=1
Voltage (on battery)
Frequency (on battery)
Transfer Time
UPS Design Technology
Output Wave Form
Total Harmonic distortion (THD)
Crest Factor
20000W
220V, 230V, 240V, +/-1% (selectable output voltage), 1Ø 2Wires
50/60 Hz +/-0.1%
0 ms
Online double conversion design
Pure Sinewave
≤2% (linear load), ≤5% (non linear load)
3:1
 
Efficiency 
AC Mode
Battery Mode
96%
95%
 
Protection 
Overload Protection
Short Circuit Protection
110% for 10min, 130% for 1min, >130% for 3sec
UPS output cut off immediately using input fuse/circuit breaker protection
 
System Display 
LCD indicators
UPS status, load level, battery level, input/output voltage, discharge time and fault indicators
 
Alarm 
Battery Mode
Low Battery
Overload
Fault
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
 
Battery 
Battery Type
Typical Recharge Time
Charging Current
Battery number
Back up time(1/2 Load)
12V 9Ah
9 hours to 90% capacity
2A
20 x2 strings
10~15 min depending on load
 
Communication 
USB, RS-232, AS-400**
SNMP**
Compatibility
Interface with power management software
Power Management from SNMP manager and web browser
Supports Windows family, Linux, Unix and Mac
 
Physical 
W x D x H mm
Net Weight Kgs(lbs)
UPS: 438 X 668 x 266[6U] Battery Pack:438 x 580 x 133[3U] x 2 pcs
UPS: 45 (99lbs) Battery: 63 (138.6lbs)x2pcs
 
Environment 
Ambient operation
Audible noise
Maximum elevation at 1000m, 0 to 40°C, 0 to 95% humidity (non-condensing)
<65dBA at 1 Meter
 
Standards & Certifications 
Performance
Safety
EMC (EMS / EMI)
Design, production, and services
Environment
Marking & Certificationsment
EN50091-3/IEC 62040-3
UL 1778, CE, EN 50091-1,EN 60950 (RD/), IEC 60950

IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-3-2/-3,FCC Part 15, CISPR 22,
EN 50091-2/IEC62040-2 Class A EN 55022/B,FCC 47 part 15 - Subpart B -

ISO 9001
ISO 14001 certified company
CE, TUV/GS, UL, cUL, c-Tick
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P=Prating x N/20
NOTE 1: Derate to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
NOTE 2: If the UPS is installed or used in a place where the altitude is above than the rated altitude, the output power must be derated one percent per 100m.
** For optional features